I’m a little wary of plug-in solar in the US. Some of the bills propose allowing 1200 watt panels which can overload wiring depending on what else is on the circuit and how in the wall wiring is run. Limiting plug-in panel wattage to, say, 400 watts might be necessary

  • A_Union_of_Kobolds
    link
    fedilink
    arrow-up
    17
    ·
    14 days ago

    Could be an issue for older homes with 14g branch circuits, but honestly i dont see 1200 watts being much of an issue on 20A circuits with 12g wire. Code required pretty much all branch circuits to be GFCI or AFCI protected now as well. Obviously that doesn’t mean anything for older homes that haven’t been updated yet, but AFCIs will catch the problems. Almost too aggressively.

    1200 watts is only 10 amps, and branch circuits are laid out much more sensibly now than in previous decades.

    Idk, as long as the home isnt like a double-wide from the 70s it should be fine.

      • A_Union_of_Kobolds
        link
        fedilink
        arrow-up
        17
        ·
        14 days ago

        I mean, yes. That’s how I make my living, im an electrician. But once again, supplying 10 amps is really not a risk in the majority of cases imo

        • silence7@slrpnk.netOP
          link
          fedilink
          arrow-up
          3
          arrow-down
          6
          ·
          14 days ago

          My big concern is that somebody plugs a panel in plus two high-amp appliances, like a space heater and a microwave, in a sequence that means they don’t trip a breaker.

          • A_Union_of_Kobolds
            link
            fedilink
            arrow-up
            26
            ·
            14 days ago

            Microwave on a dedicated circuit above counter in kitchens and gfci protected per code

            You’re not putting a space heater on your kitchen counter

            And once again youre supplying up to 1200w, not drawing 1200w. Any power supply system will just be matching the load being drawn

            I really dont think this is the degree of a problem you think it is

            • LaLuzDelSol
              link
              fedilink
              arrow-up
              2
              ·
              12 days ago

              No there is a real concern there. Suppose you have a daisy chain that goes breaker - PV panel - load. Say you have 20A draw on the load - enough to trip a 15A breaker, but the PV is providing 10A. In that case you only have 10A at the breaker, but your wires will be significantly over-current.

            • cynar
              link
              fedilink
              English
              arrow-up
              1
              ·
              13 days ago

              I think the issue is that, if you have a circuit designed and protected for X, then put Y solar in, you can get a situation where X+Y is flowing down some of the wires. It’s more than they are rated for, but the breaker doesn’t see it.

                • cynar
                  link
                  fedilink
                  English
                  arrow-up
                  2
                  ·
                  12 days ago

                  What matters is the differential. A breaker limits the input. E.g. to 16A. A plug in solar provides an independent input. E.g. 10A. Under certain circumstances, multiple loads, up to 26A total could exist on the spur, without the breaker being triggered. This could put up to 26A down some of the wiring of the spur.